KJAAMVDM
Armoured instrumentation cable for outdoor digital and analog installation.
Description
Standards
- Testing EN 50289-x-x, EN 50290-x-x.
- Reaction to fire: Fca
Construction
- Conductor: Stranded tinned copper.
- Insulation: Solid PE.
- Pair: Two conductors twisted together with an earth conductor. Each pair individually shielded with plastic-aluminium tape. Each pair is identified by a number tape. In pairs all a-conductors are blue and b-conductors are red coloured.
- Unit: Two or four pairs are stranded together to form a unit.
- Common screen: Plastic-aluminium tape with earth conductor.
- Inner sheath: Grey (RAL 7035) HFFR.
- Armouring: Both side plastic-coated corrugated steel-tape applied longitudinally over an inner sheath. Nominal thickness of the steel tape is 0,15 mm.
- Outer sheath: Black PE.
All of our fibre optic and copper cables are halogen-free.
Properties
Product information
| Nestor Code | Size | Diameter | Weight | Length | Drum |
|---|---|---|---|---|---|
| L10513 | 4x(2+1)x0,5 | 16.4 mm | 262 kg/km | 1000 m | K12 |
| L10516 | 8x(2+1)x0,5 | 19.5 mm | 382 kg/km | 1000 m | K12 |
| L10517 | 12x(2+1)x0,5 | 22.6 mm | 501 kg/km | 1000 m | K14 |
| L10518 | 24x(2+1)x0,5 | 27.9 mm | 833 kg/km | 1000 m | K18 |